*1
Set the offset value and gain value in the user range setting within the range satisfying the following conditions.
If the following conditions are not satisfied, A/D conversion may not be properly performed.
• gain value ≤ 20mA, offset value ≥ 0mA
• ((gain value) - (offset value)) ≥ 16.0mA
*2
When analog input is performed exceeding the range of digital output value, the digital output value is fixed to the
maximum or minimum.
Input range setting
4 to 20mA
0 to 20mA
4 to 20mA (Extended mode)
User range setting
*3
This is the maximum resolution in user range setting.
● Use the value within the practical analog input range and practical digital output range. If a value is out of the range, the
resolution and accuracy may not fall within the range of performance specifications. (Do not use the value in the dotted
line region in the graph of current input characteristic.)
● Do not input a value of ±30mA or more. This may damage the elements.
Digital output value
Minimum
-480
-5480
-20480
APPENDICES
Maximum
20479
22979
20479
207