Mitsubishi L Series User Manual page 171

Analog-digital converter module
Hide thumbs Also See for L Series:
Table of Contents

Advertisement

(4) Offset/gain setting mode flag (XA)
(a) Offset/gain setting mode
When registering the value, which was adjusted with the offset/gain setting, to the module, use Offset/gain setting
mode flag (XA) as an interlock condition to turn User range write request (YA) OFF → ON → OFF.
For the offset/gain setting, refer to the following.
• Offset/gain setting (
Module READY (X0)
Offset/gain setting mode
flag (XA)
User range write request (YA)
(b) Normal mode
In the user range restoration, use Offset/gain setting mode flag (XA) as an interlock condition to turn User
range write request (YA) OFF → ON → OFF.
For user range restoration, refer to the following.
• Save/restoration of offset/gain value (
Module READY (X0)
Offset/gain setting mode flag (XA)
User range write request (YA)
(5) Channel change completed flag (XB)
When changing a channel to perform the offset/gain setting, use Channel change completed flag (XB) as an
interlock condition to turn Channel change request (YB) OFF → ON → OFF.
For the offset/gain setting, refer to the following.
• Offset/gain setting (
Offset/gain setting mode Offset
specification (Un\G22),
Gain specification (Un\G23)
Channel change completed
flag (XB)
Channel change request (YB)
Page 54, Section 7.5)
Controlled by the A/D converter module
Controlled by the program
OFF
ON
OFF
Page 124, Section 8.19)
Controlled by the A/D converter module
Controlled by the program
ON
Page 54, Section 7.5)
Controlled by the A/D converter module
Controlled by the program
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
APPENDICES