When a value out of the setting range above is set to a channel, an error occurs in the channel, an error code is stored in
Latest error code (Un\G19) and Error flag (XF) is turned to ON. The operation is performed in the setting configured before
the error occurrence.
(23)CH
Shifting amount to conversion value (Un\G150 to Un\G153)
Set the shifting amount to conversion value that is to be used for the shift function.
For details on the shift function, refer to the following.
• Shift function (
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5
Sign bit
1: Negative
0: Positive
(a) Setting range
Setting range is -32768 to 32767.
(b) Enabling the setting
• When the value is set, set shifting amount to conversion value turns valid regardless of turning Operating
condition setting request (Y9) OFF → ON → OFF.
(c) Default value
All channels are set to Disable (0).
(24)Mode switching setting (Un\G158, Un\G159)
Set the setting value for the mode to be switched to.
Mode switching to
Normal mode
Offset/gain setting mode
(a) Enabling the setting
Turn OFF → ON → OFF Operating condition setting request (Y9) to enable the setting.
(b) After the mode is switched
When the mode is switched, this area is cleared to zero and Operating condition setting completed flag (X9) is
turned to OFF.
After checking that the operating condition setting complete/completion flag is OFF, turn Operating condition
setting request (Y9) to OFF
When a value out of the setting range above is written, the mode is not switched and only the operating condition is
changed.
Page 86, Section 8.11)
Data section
Un\G158
b4
b3
b2
b1
b0
Setting value
0964
H
4144
H
APPENDICES
Un\G159
4144
H
0964
H
185