Analog-digital converter module
Hide thumbs Also See for L Series:
Table of Contents

Advertisement

(38)Level data
This is the area for storing the data to be monitored when the level trigger of the logging function is used. 10 types
of data are available: Level data 0 (Un\G1072) to Level data 9 (Un\G1081)
Use Level data
generate triggers.
• Logging function (
(a) Application example
To monitor data register D100 in the CPU module and operate the level trigger in CH1, create a program as
follows.
1.
Set 1073 (Level data 1) for CH1 Trigger data (Un\G1064). (When Level data 1 is used)
2.
Store the storage data which is D100 in the program in Level data 1 (Un\G1073) as needed. (The
start I/O number is set to 10
(b) Setting range
Setting range is -32768 to 32767.
(c) Default value
All are set to 0.
(39)CH
Trigger setting value (Un\G1082 to Un\G1085)
When the logging function is used, set a level where a level trigger is generated.
For details on the logging function, refer to the following.
• Logging function (
(a) Setting range
Setting range is -32768 to 32767.
(b) Enabling the setting
Turn OFF → ON → OFF Operating condition setting request (Y9) to enable the setting.
(c) Default value
All channels are set to 0.
194
(Un\G1072 to Un\G1081)
(Un\G1072 to Un\G1081) to monitor device values in other than the A/D converter module and
Page 98, Section 8.14)
in the following program example.)
H
Page 98, Section 8.14)