3: When values are set for a channel with input range of 1 to 5V (Extended mode) as follows:
Ex.
• "Scaling upper limit value": 16000
• "Scaling lower limit value": 4000
The digital output values and scaling values (digital operation values) are as follows:
Scaling upper limit value:
16000
Analog input voltage (V)
84
Digital output value
20000
Scaling lower limit value:
4000
0
1
2
3
4
5
5.5
0
Analog input voltage (V)
0
5
1
Digital output value
-5000
0
5000
10000
15000
20000
22500
Scaling value
(digital operation value)
1000
4000
7000
10000
13000
16000
17500