Mitsubishi L Series User Manual page 85

Analog-digital converter module
Hide thumbs Also See for L Series:
Table of Contents

Advertisement

2. When values are set for a channel with input range of -10 to 10V as follows:
Ex.
• "Scaling upper limit value": 16000
• "Scaling lower limit value": 4000
The digital output values and scaling values (digital operation values) are as follows:
Scaling upper limit value 16000
Scaling lower limit value 4000
Analog input voltage (V)
-10
-5
0
5
10
Digital output value
20000
-20000
-10
0
10
Digital output value
-20000
-10000
0
10000
20000
CHAPTER 8 FUNCTIONS
Analog input voltage (V)
Scaling value
(digital operation value)
4000
7000
10000
13000
16000
8
83