(4) Initial setting description
(a) Channel setting
Item
A/D conversion enable/disable setting Enable
Averaging process setting
Time Average/ Count Average/
Moving Average
Conversion speed setting
Warning output setting
Process alarm upper upper limit value 0
Process alarm upper lower limit value
Process alarm lower upper limit value
Process alarm lower lower limit value
Input signal error detection setting
Input signal error detection setting
value
Input signal error detection extension
setting
Scaling enable/disable setting
Scaling upper limit value
Scaling lower limit value
Shifting amount to conversion value
Digital clipping function enable/
disable setting
(b) Device for user
Device
D1(D11)
D2(D12)
D8
D10
D18
D28(D13)
M0
M1
M2
M20 to 27
M50 to 53
M100
X40
X43
X44
Y50 to 5F
CH1
CH2
Enable
Sampling
Count average
processing
0
50 times
20µs
Disable
Enable
20000
0
18000
0
3000
0
0
Enable
Disable
10.0%
5.0%
Disable
Disable
Disable
Disable
0
0
0
0
0
0
Disable
Disable
CH1 Digital output value
CH2 Digital output value
Input signal error detection flag
Error code
Warning output flag
CH3 Scaling value (digital operation value)
CH1 A/D conversion completed flag
CH2 A/D conversion completed flag
CH3 A/D conversion completed flag
Warning output flag
Input signal error detection flag
Module READY checking flag
Digital output value read command input signal
Input signal error detection reset signal
Error reset signal
Error code notation (BCD 3 digits)
CHAPTER 10 PROGRAMMING
Description
CH3
Enable
Disable
Sampling
Moving average
processing
10 times
0
Disable
Disable
0
0
0
0
0
0
0
0
Disable
Disable
5.0%
5.0%
Disable
Disable
Enable
Disable
32000
0
0
0
10000
0
Enable
Disable
Description
LX40C6 (X40 to 4F)
LY42NT1P (Y50 to 5F)
10
CH4
143

Advertisement

Table of Contents
loading

This manual is also suitable for:

L60ad4

Table of Contents