Mitsubishi L Series User Manual page 164

Analog-digital converter module
Hide thumbs Also See for L Series:
Table of Contents

Advertisement

Error code
(decimal)
CH
Logging points after trigger (Un\G1048 to Un\G1051) is set to
*1
a value outside the range of 1 to 10000.
204
The channel where the error has occurred fits in
CH
Level trigger condition setting (Un\G1056 to Un\G1059) is set
*1
to a value outside the range of 0 to 3.
205
The channel where the error has occurred fits in
CH
Trigger data (Un\G1064 to Un\G1067) is set to a value outside
*1
the range of 0 to 4999.
206
The channel where the error has occurred fits in
CH
Logging hold request (Un\G1008 to Un\G1011) is set to a
*1
value other than 0 and 1.
207
The channel where the error has occurred fits in
CH
Logging enable/disable setting (Un\G1000 to Un\G1003) is set
to Enable (0), and besides the input signal error detection function
*1
208
or the input signal error detection extension function is enabled.
The channel where the error has occurred fits in
CH
Flow amount integration enable/disable setting (Un\G1300 to
Un\G1303) is set to a value other than 0 and 1.
The channel where the error has occurred fits in
*1
210
Conversion speed is set to 20µs or 80µs, and besides CH
amount integration enable/disable setting (Un\G1300 to Un\G1303)
is set to Enable (0).
The channel where the error has occurred fits in
CH
Integration cycle setting (Un\G1308 to Un\G1311) is set to a
*1
value outside the range of 1 to 5000.
211
The channel where the error has occurred fits in
The set value in CH
Un\G1311) is shorter than the update cycle of CH
*1
212
(digital operation value) (Un\G54 to Un\G57).
The channel where the error has occurred fits in
CH
Flow amount time unit setting (Un\G1316 to Un\G1319) is set
*1
to a value outside the range of 0 to 2.
213
The channel where the error has occurred fits in
CH
Unit scaling setting (Un\G1324 to Un\G1327) is set to a value
*1
outside the range of 0 to 4.
214
The channel where the error has occurred fits in
CH
Flow amount integration temporary stop request (Un\G1356 to
*1
Un\G1359) is set to a value other than 0 and 1.
215
The channel where the error has occurred fits in
162
Description and cause of error
Integration cycle setting (Un\G1308 to
Set a value within the range of 1 to 10000 in CH
Logging points after trigger (Un\G1048 to
.
Un\G1051).
Set one of the following values in CH
condition setting (Un\G1056 to Un\G1059).
• Disable (0)
• Above (1)
.
• Below (2)
• Pass through (3)
Set a value within the range of 0 to 4999 in CH
Trigger data (Un\G1064 to Un\G1067).
.
Set OFF (0) or ON (1) in CH
(Un\G1008 to Un\G1011).
.
To use the logging function, set the following buffer
memory areas as below.
• Set Disable (0) in Input signal error detection
extension setting (Un\G27)
.
• Set Disable (1) in Input signal error detection
setting (Un\G47).
Set Enable (0) or Disable (1) in CH
integration enable/disable setting (Un\G1300 to
.
Un\G1303).
Flow
To use the flow amount integration function, set the
conversion speed to 1ms.
.
Set a value within the range of 1 to 5000 in CH
Integration cycle setting (Un\G1308 to Un\G1311).
.
Set CH
Un\G1311) so that the integration cycle is equal to or
longer than the update cycle of CH
(digital operation value) (Un\G54 to Un\G57).
Scaling value
For the setting method of the integration cycle, refer
to the following.
.
Flow amount integration function (
Section 8.15)
Set one of the following values in CH
time unit setting (Un\G1316 to Un\G1319).
• /s (0)
.
• /min (1)
• /h (2)
Set one of the following values in CH
setting (Un\G1324 to Un\G1327).
• × 1 (0)
• × 10 (1)
.
• × 100 (2)
• × 1000 (3)
• × 10000 (4)
Set No request (0) or Temporary stop request (1) in
CH
Flow amount integration temporary stop
.
request (Un\G1356 to Un\G1359).
Action
Logging hold request
Flow amount
Integration cycle setting (Un\G1308 to
Scaling value
Flow amount
Level trigger
Page 110,
Unit scaling