Mitsubishi L Series User Manual page 193

Analog-digital converter module
Hide thumbs Also See for L Series:
Table of Contents

Advertisement

(34)CH
Logging cycle setting value (Un\G1032 to Un\G1035), CH
unit setting (Un\G1040 to Un\G1043)
Set the cycle of storing the logging data.
Set a value for 1 cycle in CH
Set a unit of cycle in CH
For details on the logging function, refer to the following.
• Logging function (
(a) Setting range
The available setting range of CH
setting for CH
Logging cycle unit setting (Un\G1040 to Un\G1043).
Logging cycle
unit
µs
ms
s
(b) Actual logging cycle
The actual logging cycle is an integral multiple of the conversion cycle of digital output value or scaling value
(digital operation value).
When the conversion cycle is set to 80µs and the A/D conversion is performed for CH1 to CH3 with the
Ex.
sampling processing
→ The actual logging cycle is an integral multiple of 240µs (80µs × 3) with the value set in CH
setting value (Un\G1032 to Un\G1035) and CH
upper limit value.
(c) Enabling the setting
Turn OFF → ON → OFF Operating condition setting request (Y9) to enable the setting.
(d) Default value
• For CH
Logging cycle setting value (Un\G1032 to Un\G1035), all channels are set to 4.
• For CH
Logging cycle unit setting (Un\G1040 to Un\G1043), all channels are set to ms (1).
● In the channel where the following conditions are set, an error occurs. Then, the error code is stored in Latest error code
(Un\G19), Error flag (XF) is turned to ON and logging cannot be performed.
• When a value out of the above setting range is set in either of CH
Un\G1035) or CH
• When the set logging cycle is below the update cycle of data to be logged
● When CH
Logging enable/disable setting (Un\G1000 to Un\G1003) is set to Disable (1), the setting for CH
cycle setting value (Un\G1032 to Un\G1035) and CH
Logging cycle setting value (Un\G1032 to Un\G1035).
Logging cycle unit setting (Un\G1040 to Un\G1043).
Page 98, Section 8.14)
Logging cycle setting value (Un\G1032 to Un\G1035) depends on the
Setting value of CH
Logging cycle
unit setting (Un\G1040 to Un\G1043)
0
1
2
Logging cycle unit setting (Un\G1040 to Un\G1043) as the
Logging cycle unit setting (Un\G1040 to Un\G1043)
Available setting range of CH
cycle setting value (Un\G1032 to
Logging cycle setting value (Un\G1032 to
Logging cycle unit setting (Un\G1040 to Un\G1043) are ignored.
APPENDICES
Logging cycle
Logging
Un\G1035)
80 to 32767
1 to 32767
1 to 3600
Logging cycle
Logging
191