To get the input data again, the T-bit has to be reset again. If a command of the
command interface with DP V1 is being carried out, setting the toggle bit is not
necessary.
10.5.2

Store current configuration to the AS-i master

1. Switch master to configuration mode
2. Write the current slave configuration to the master
3. Switch master to protected mode
4. Wait until master is in normal (protected) operation mode
12-byte management
1. Switch master to config mode
Byte 1
Byte 2
Byte 3
Byte 4
...
Byte 12
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Request
00
hex
...
00
hex
Response
50
hex
80
(toggle bit, master1)
hex
16-bit channel 1 high byte
16-bit channel 1 low byte
16-bit channel 2 high byte
16-bit channel 2 low byte
16-bit channel 3 high byte
16-bit channel 3 low byte
16-bit channel 4 high byte
16-bit channel 4 low byte
00
not used
hex
00
not used
hex
Request: SET_OP_MODE
0C
(SET_OP_MODE)
hex
00
(T = 0, master 1, single master)
hex
01
(= config mode)
hex
00
hex
...
00
hex
AS-i/PROFIBUS-Gateway
Command Interface
hex
hex
hex
hex
hex
hex
hex
hex