Slave Test Tool - Pepperl+Fuchs VBG-PB-K20-DMD-C1 Manual

As-interface/profibus-gateway
Table of Contents

Advertisement

To give the slave a new address choose the menu entry "NEW ADDRESS". After-
wards the address can be selected with the help of the arrow buttons.The (re-)
addressing is carried out by selecting the menu entry "PRG" and pressing the OK
button.
If an error occurs while addressing a slave, one of the following error messages is
displayed for about 2 seconds:
Failed: SND:slave with old address has not been detected.
Failed: SD0:slave with address zero has been detected.
Failed: SD2:slave with new address has been detected.
Failed: DE:could not delete old address.
Failed: SE:error setting new address.
Failed: AT:new address could be stored temporarily only.
Failed: RE:error reading the extended ID-code 1.
7.4

Slave Test Tool

With this function a single AS-i slave can be tested.
Please note that you must have selected the desired AS
and the OK button when you operate a device with two AS-i circuits (see chapter
7.5.1)
Now a warning message is displayed, that possibly by this test outputs are set and
the host may loose control of the circuit.
To start the test press the OK button, to cancel press the button ESC.
In the following menu the slave to be tested has to be chosen by selecting the sla-
ve address.
Subject to reasonable modifications due to technical advances.
28
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Operating in Advanced Display Mode
S L AV E A D R T O O L
O L D A D D R E S S
2 1 A
N E W A D D R E S S
0 3 B
P R G
A S - I C I R C U I T 1
A S - I C I R C U I T 2
WA R N I N G :
O U T P U T S M AY B E
S E T A N D H O S T M AY
L O S E C O N T R O L
AS-Interface
-
i circuit using the arrow
Copyright Pepperl+Fuchs, Printed in Germany

Advertisement

Table of Contents
loading

Table of Contents