A duplicate address causes a configuration error und will be shown in the diplay of
the master.
Duplicate addresses can be recognized only in the AS-i segment directly at
the master. If both slaves participate in a duplicate address located behind a
repeater, the duplicate address' recognition is impossible.
8.4.2

Earth fault detector

An Earth Fault exists when the voltage
is outside of the following range:
This error limits the fail-safe characteristic of the AS-i transmission substantially.
Earth faults are indicated in the master´s display and AS-i Control Tools.
By a double master in version 1 power supply for 2 AS-i ciruits an earth fault in
one of the both circuits causes also an earth fault in the other circuit because
of the existing galvanic connection.
For recognition of earth faults the master must be grounded with the function
earth.
8.4.3

Noise detector

The noise detector detects alternating voltages on AS-i, which are not produced
by AS-i master or AS-i slaves. These interference voltages can cause telegram
disturbances.
A frequent cause are insufficiently shielded frequency inverters or awkwardly shif-
ted cables.
Noises are indicated in the master´s display and the AS-i Control Tools.
8.4.4

Overvoltage detector

Overvoltages are present, if the AS-i line, whose conductors lie normally electri-
cally symmetrically to the plant earth, are strongly electrically raised. A cause can
be e.g. power-on procedures of large consumers. However sometimes overvolta-
ges don´t generally disturb AS-i communication, but can release incorrect signals
of sensors.
Overvoltages are indicated in the master´s display and the AS-i Control Tools.
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Advanced Diagnostics for AS-i Masters
U
≤ U
≤ 90% U
10% U
AS-i
GND
AS-i/PROFIBUS-Gateway
(Nominal value of U
GND
AS-i
Copyright Pepperl+Fuchs, Printed in Germany
=0,5 U
.)
GND
AS-i
49

Advertisement

Table of Contents
loading

Table of Contents