Control/Status Byte; Table 16: Control Byte C0; Table 17: Status Byte S0 - WAGO 753-1630 Manual

Smi master module 230 v ac
Table of Contents

Advertisement

40
Process Image
Pos: 77 /Serie 753 (WAGO-I/O-SYSTEM)/Prozessabbild Klemmenbus/FT&K/Prozessabbild 753-1630, -1631/Prozessabbild 753-1630, -1631 - Control-/Statusbyte @ 28\mod_1478705543803_21.docx @ 386878 @ 2 @ 1
5.1

Control/Status Byte

The control/status byte is shown in the process image independent of user-
specific parameterization of the SMI master module.
If bit 7 is set in the control byte, register communication is always active and
process data communication inactive.

Table 16: Control Byte C0

Bit 7
RegCom
-
--
Mailbox
RegCom
In the status byte, only another diagnostic is shown next to the diagnostic of a
general error in the event of an error. If several errors are detected at the same
time, the diagnostic with the highest priority is shown (see table below).

Table 17: Status byte S0

Bit 7
RegCom
-
Field-side
supply
Short circuit
Mailbox
General Error
RegCom
Pos: 78 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Manual
Version 1.2.0 FW/HW Version 02/01
Control byte C0
Bit 6
Bit 5
--
Mailbox
Not used
Reserved
Mailbox 2.0 in the process data
0 – Mailbox deactivated
1 – Mailbox activated
Register communication
0 – Register communication deactivated
1 – Register communication activated
Status Byte S0
Bit 6
Bit 5
General
Mailbox
Error
Not used
Undervoltage field supply
0 – Power supply is sufficient.
1 – Power supply is too low
SMI short circuit detection:
0 – No short circuit detected
1 – Short circuit on the SMI connections detected
Mailbox 2.0 in the process data:
0 – inactive
1 – active
General error status with inactive register
communication:
0 – inactive
1 – active
Register communication:
0 – inactive
1 – active
753-1630 SMI Master Module 230 V AC
Bit 4
Bit 3
Bit 2
-
-
Bit 4
Bit 3
Bit 2
Short
Field
circuit
supply
Bit 1
Bit 0
-
-
-
Bit 1
Bit 0
-
-
-
Medium priority
Low priority
High priority