Positioning Curtains And Slats; Table 14: Behavior Of Smi Drives And Curtains With Button Presses - WAGO 753-1630 Manual

Smi master module 230 v ac
Table of Contents

Advertisement

30
Function Description

Table 14: Behavior of SMI Drives and Curtains with Button Presses

Function
Long button
press
Short button
press when
stopped
Short button
press when
moving
Pos: 71.6 /Serie 753 (WAGO-I/O-SYSTEM)/Funktionsbeschreibung/Funktionsbeschreibung 753-1630, -1631/Funktionsbeschreibung 753-1630, -1631 - Feldbuskopplermodus -Positionieren von Behängen und Lamellen @ 28\mod_1478704015085_21.docx @ 386520 @ 3 @ 1
4.1.5

Positioning Curtains and Slats

The position of a shutter is determined by the shutter position and slat position.
The shutter position is a position in the total adjusting range of shutters between
the top and bottom end positions of the drive.
The slat position is a position between fully open and fully closed slats in the slat
adjusting range (total travel range).
Both values are specified in percent.
The shutter position is adjusted first. The slats are then positioned. The slats are
always positioned from the fully open slat position that is reached by moving
upwards. The distances of this motion can be individually set by configuring the
positioning offset for each shutter. The adjusting range of the slats must be less
than the positioning offset.
Manual
Version 1.2.0 FW/HW Version 02/01
Behavior of SMI Drives
SMI drives are moved to the end
position.
SMI drives are rotated by the
configured angular degree.
SMI drives are stopped.
753-1630 SMI Master Module 230 V AC
Behavior of Curtains
Curtains are moved up or down
completely.
Slats are opened or closed
completely.
Curtains are moved up or down
by the configured increment.
Slats are adjusted by the
configured angular degree.
Curtains are stopped.
Slats remain in the current
position.