Mounting; Mounting Sequence - WAGO 753-1630 Manual

Smi master module 230 v ac
Table of Contents

Advertisement

753-1630 SMI Master Module 230 V AC
Pos: 88 /Alle Serien (Allgemeine Module)/Überschriften/Ebene 1/Montieren - Überschrift 1 @ 3\mod_1225446744750_21.docx @ 24900 @ 1 @ 1
6

Mounting

Pos: 89 /Serie 753 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen/Sicherheits- und sonstige Hinweise/Gefahr: Zugänglichkeit zum SMI-Bus einschränken - Berührbare spannungsführende Teile @ 31\mod_1526651076104_21.docx @ 488469 @ @ 1
Restrict accessibility to the SMI bus
The SMI bus can be declared as a communication interface that is considered
accessible to the operator according to DIN EN 61010-2-201. The interface is
generally part of the fixed installation of the SMI master module.
According to the SMI specification, the bus voltage is limited to max. 60 VAC.
Because of the option to connect multiple SMI drives, the current on the SMI bus
exceeds the limiting values for accessible parts acc. DIN EN 61010.
Due to the resulting risk of personal injury from electric shock, accessibility to the
SMI bus must be restricted.
Pos: 90.1 /Serie 750 (WAGO-I/O-SYSTEM)/Montieren/Demontieren/Montagereihenfolge @ 3\mod_1231770210031_21.docx @ 25992 @ 2 @ 1
6.1

Mounting Sequence

Fieldbus couplers/controllers and I/O modules of the WAGO-I/O-SYSTEM 750
are snapped directly on a carrier rail in accordance with the European standard
EN 50022 (DIN 35).
The reliable positioning and connection is made using a tongue and groove
system. Due to the automatic locking, the individual devices are securely seated
on the rail after installation.
Starting with the fieldbus coupler/controller, the I/O modules are mounted
adjacent to each other according to the project design. Errors in the design of the
node in terms of the potential groups (connection via the power contacts) are
recognized, as the I/O modules with power contacts (blade contacts) cannot be
linked to I/O modules with fewer power contacts.
Pos: 90.2 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen/Sicherheits- und sonstige Hinweise/Vorsicht/Vorsicht: Verletzungsgefahr durch scharfkantige Messerkontakte! @ 6\mod_1256193279401_21.docx @ 43414 @ @ 1
Risk of injury due to sharp-edged blade contacts!
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent
injury.
Pos: 90.3 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen/Sicherheits- und sonstige Hinweise/Achtung/Achtung: I/O-Module nur in vorgesehener Reihenfolge stecken! @ 6\mod_1256194177073_21.docx @ 43429 @ @ 1
Insert I/O modules only from the proper direction!
All I/O modules feature grooves for power jumper contacts on the right side. For
some I/O modules, the grooves are closed on the top. Therefore, I/O modules
featuring a power jumper contact on the left side cannot be snapped from the
top. This mechanical coding helps to avoid configuration errors, which may
destroy the I/O modules. Therefore, insert I/O modules only from the right and
from the top.
Pos: 90.4 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen/Sicherheits- und sonstige Hinweise/Hinweis/Hinweis: Busabschluss nicht vergessen! @ 6\mod_1256194225557_21.docx @ 43432 @ @ 1
Version 1.2.0 FW/HW Version 02/01
Mounting