3. Diagnosis
3.3
Diagnosis with PROFIBUS-DP
3.3.1 Diagnostic words
Festo P.BE-CP-FB13-E-EN en 0112e
The CP system supports diagnostic possibilities via the PRO-
FIBUS in accordance with EN 50170 (DIN 19245) (The device-
specific diagnosis is supported).
Please note
The identifier-related or channel-related diagnosis listed in
EN 50170 (DIN 19245) is not supported.
The following error states of the CP system are grouped into
diagnostic words and passed on to the programmer.
–
Load voltage failure on the output modules
–
Short circuit/overload at the output modules
–
Interruption in CP connection on various CP modules
Additional error messages (DIL switch 2 = ON):
–
Load voltage failure on the CP connection
Drop below tolerance in voltage for CP valves ( < 20.4 V)
–
3-9