2. Commissioning
Octet
Designation
2 and 3
WD_Fact_1
WD_Fact_2
4
Minimum Station Delay
Responder (min T
5 and 6
Ident_Number
7
Group_Ident
8...32
User_Prm_Data
2.3.3 Send configuration data
2-38
Further octets
Explanation
Range 1...255: The response monitoring time of
the CP system is transferred with these two octets:
TWD [s] = 10 ms x WD_Fact_1 x WD_Fact_2
The minimum time the CP system must wait before
)
the reply telegram may be sent to the DP master.
SDR
Transfer the Ident number (= F13C) of the CP
system; parametrizing telegrams to the CP system
will only be accepted if the transferred and the
programmed Ident numbers are the same.
Not supported by the CP system
Not supported by the CP system
The configuration data are transmitted from the DP master to
the CP system with the function Chk_Cfg.
Please note
The configuration of a CP system must be carried out as
follows:
– per string: a DP identifier for inputs and outputs.
– via sum identifier: sum of the input bytes and sum of the
output bytes.
Festo P.BE-CP-FB13-E-EN en 0112e