2. Commissioning

2.3.7 Bus parameter/reaction times

2.3.8 Transmission times on the PROFIBUS-DP

Festo P.BE-CP-FB13-E-EN en 0112e
Baud rate
max T
(kBaud)
...187.5
500
1500
3000
6000
12000
Please note
S Note here the cycle time of your PLC and the update time
of the PROFIBUS-DP.
The delay time within the CP system depends on the amount
of data and, therefore, on the string assignment. It amounts
to: < 5 ms.
Please refer to your controller manual for calculating the total
transmission time.
(T
)
min T
(T
SDR
Bit
SDR
60
100
150
11
11
250
450
800
)
Bit
2-43