Festo CP-FB13-E Programming And Diagnostics Manual page 106

Compact performance
Hide thumbs Also See for CP-FB13-E:
Table of Contents

Advertisement

A. Technical data and index
Load voltage for solenoid valves of CP valve terminal
Pin 2
Power supply connection
– Rated value
– Tolerance
Current consumption
– Pin 2 node FB13-E
Residual ripple
Bridging time during logic voltage failure
Field bus
Design
Transmission type
Protocols
Baud rate
Cable length (depends on baud rate and cable
type)
Cable type (depends on cable length and field
bus baud rate set)
Loading capacity of power supply positive (P5V)
pin 6
Electromagnetic compatibility
– Interference emission
– Immunity to interference
A-4
24 V DC
20.4...26.4 V
Sum of all switched-on CP solenoid valves;
see manual "CP pneumatics"
4 Vpp (within tolerance)
20 ms
RS 485, floating
Serial asynchronous, half-duplex
PROFIBUS-DP
9.6...12000 kBaud
automatic baud rate recognition
Up to 23.8 km
See manual for your controller
Max. 40 mA
Tested as per EN 55011, limit value B
Tested as per EN 50082-2
Festo P.BE-CP-FB13-E-EN en 0112e