2. Commissioning
Festo P.BE-CP-FB13-E-EN en 0112e
Standard mode
In standard mode configure 16 outputs and 16 inputs per as-
signed string. DP identifier: 049 or 16DX for each assigned
string.
The following table provides a summary of the possible entries
for the valve terminal in standard mode.
Last used
Number of
string number
inputs/outputs
0
2
1
4
2
6
3
8
Fig. 2/3: Standard mode: Possible configuration of the
inputs and outputs
The last used string is decisive for the number of DP ident-
ifiers, even if numerically lower strings are not assigned (see
manual "CP system, installation and commissioning").
Example:
CP system with 3 strings, a total of 3 input and 3 output mod-
ules, highest assigned string number = 2.
DP identifier
0
16DX
1
16DX
2
16DX
Fig. 2/4: Configuration in standard mode
Individual identifier
16DX
16DX, 16DX
16DX, 16DX, 16DX
16DX, 16DX, 16DX, 16DX
Comment
Input module and output module of
string 0
Input module and output module of
string 1
Input module and output module of
string 2
2-9