3. Diagnosis
Summary of octets 9...12: Sevice-related diagnoses 2...5
Octet
Explanation
9
Device-related diagnosis 2 string 0
10
Device-related diagnosis 3 string 1
11
Device-related diagnosis 4 string 2
12
Device-related diagnosis 5 string 3
Fig. 3/9: Summary of octets 9...12
Octets 9...12: Device-related diagnoses 2...5
Bit
Meaning
0
I
out
1
I
on
2
Short circuit/overload
3
V
out
4
V
sen
5
V
val
6
V
load
7
Ex
Heavy print = Valve terminal related bits
*
With DIL switch S2 = ON
Fig. 3/10: Diagnostic bits of device-related diagnoses 2...5
3-16
Structure of device-related diagnoses 2...5
Explanation
Logical "1": CP connection interrupted on output module
Logical "1": CP connection interrupted on input module
Logical "1": Short circuit/overload at output module
Logical "1": Load voltage failure on output module
Logical "1": Short circuit/overload in sensor supply
voltage < 10 V
Load voltage for valve coils < 20.4 V
*
Logical "1":
Load voltage for valve coils < 10 V
*
Logical "1":
Logical "1": (no significance)