3. Diagnosis
Octet 2: station status_2
Bit
Meaning
0
Diag.Prm_Req
1
Diag.Stat_Diag
2
3
Diag.WD_On
4
Diag.Freeze_Mode
5
Diag.Sync_Mode
6
7
Diag.Deactivated
Heavy print = Valve terminal related bits
Fig. 3/5: Diagnostic bits of station status_2
Octet 3: station status_3
Bit
Meaning
0...6
7
Diag.Ext_Diag_Overflow
Fig. 3/6: Diagnostic bits of station status_3
Festo P.BE-CP-FB13-E-EN en 0112e
Structure of station status 2
Explanation
Logical "1": master must configure the CP system again
Logical "1": master must request diagnostic data until
this bit is set to logical "0"
Always logical "1" (set by CP system)
Logical "1": Watchdog activated
Logical "1": Freeze activated
Logical "1": Sync activated
Reserved
Always logical "0" (set by CP system)
Structure of station status 3
Explanation
Reserved
Always logical "0" (set by CP system)