A. Technical data and index
A.1
Technical specifications of field bus node CP FB13-E
General
Temperature range:
– Operation
– Storage/transport
Relative humidity
Protection class as per EN 60529 plug connector
inserted or fitted with protective cap
Protection against electric shock
Protection against electric shock (protection
against direct and indirect contact as per
EN 60204-1/IEC 204)
Protection against explosion
(as per EU guideline 94/9/EG, EN 50021 and
EN 50281-1-1), do not disconnect when under
tension
Power supply for electronics and input modules
Pin 1
Power supply connection
– Rated value
– Tolerance
Current consumption
– Pin 1 node FB13-E
– Total electronics of the CP system
Residual ripple
Bridging time during logic voltage failure
Festo P.BE-CP-FB13-E-EN en 0112e
- 5 °C ... +50 °C
- 20 °C ... +70 °C
95 % non condensing
IP65
By PELV power unit
(Protected Extra-Low Voltage)
II 3 G/D EEx nA II T5 X - 5 °C ≤Ta ≤+ 50 °C
T 80 °C IP65 (year of manufacture see Ex-identifi-
cation on the product).
Plugs or adapters of the electric connections
must comply at least with protection class IP64!
24 V DC
20.4...26.4 V
250 mA
See manual "CP system",
Table of current consumption
4 Vpp (within tolerance)
20 ms
A-3