3. Diagnosis
3.1.3 Diagnosis LED BUS ERROR
LED
Colour
BUS
Red
ERROR
flashes fast
BUS
Red
ERROR
flashes at
1-second
intervals
BUS
Out
ERROR
3-6
Possible PROFIBUS-specific LED displays on the operating
status of the CP node can be found in the following table.
Operating status
Station number not permitted
Field bus connection not correct.
Possible causes:
– Station number not correct
(e.g. address assigned twice)
– Switched-off or defective field
bus module
– Interrupted, short-circuited or
faulty field bus connection
– Configuration not correct,
nominal • actual status
Valve test
Error treatment
S Correct station number
(0, ..., 125)
Check the ...
S Setting of the address selector
switch
S Field bus module
S Field bus connection
S Configuration
–
(Conclude valve test)
Festo P.BE-CP-FB13-E-EN en 0112e