1. Commissioning
1.3

Configuration by using process data

1.3.1 Predefined process data for establising connections
Transmit PDO 1
Transmit PDO 2
Receive PDO 1
Receive PDO 2
Fig. 1/1: Overview of PDO 1 and 2 for inputs and outputs
Festo P.BE-CTEU-CO-OP+MAINT-EN en 1101NH
The bus node can use up to two PDO telegrams for process
data (Fig. 1/1), for both inputs (TxPDO) and outputs (RxPDO).
Both telegrams are continuously filled with process data of
one or two connected devices (max. 2 x 8 bytes = 128 logical
I/Os for inputs and outputs).
I0 ... E7
I8 ... I15
I16 ...
I23
I64 ...
I72 ...
I80 ...
I71
I79
I87
O0 ...
O8 ...
O16 ...
O7
O15
O23
O64 ...
O72 ...
O80 ...
O71
O79
O87
Note
When filling the process data telegrams please note that
CANopen specification DS401 is only observed if you fill
PDO 1 exclusively with input and output bytes.