Recommended cable condition for FOUNDATION Fieldbus and PROFIBUS communication
Cable specification
Type A
18AWG
Twisted pair cable
0.8mm
(pair shielded)
Type B
22AWG
Twisted pair cable
0.32mm
(common shielded)
Type C
26AWG
Twisted pair cable
0.13mm
(unshielded)
Type D
16AWG
Straight through cable
1.25mm
(common shielded)
Source: IEC 61158-2:"Digital data communications for measurement and control – Fieldbus for use
industrial control systems – Part 2 : Physical layer specification and service definition"
NOTE: Placeable cable lengths vary depending on actual field conditions. For the details, refer to the
documents listed below:
・"PROFIBUS PA Technology and Application"
・FOUNDATION Fieldbus Application Guide AG-140; "Wiring and Installation; 31.25 kbit/s,
Voltage; Model,Wire Medium"
Recommended cable condition for Modbus communication
Cable specification
Twisted pair
Applicable rubber packing size for wire lines and sizes
Recommended wire size
Cable packing gum ID.
φ8.1 to φ9.0
φ9.1 to φ10.0
φ10.1 to φ11.0
φ11.1 to φ12.0
φ12.1 to φ13.0
φ13.1 to φ14.0
NOTE: Use shreld cables.

7.9 Terminal Identification of Separately Mounted Transmitter

Terminal
Item
name
TB20
TB21
NOTE:
※: Maximum lengths of the cable are: 50m for Type S stainless steel tube type, 100m for
Type S titanium tube type, and 5m for Type B sensors.
Max. cable
Size
Impedance
length
1900m
100Ω
2
1200m
100Ω
2
400m
no regulation
2
200m
no regulation
2
0.75mm
2sq
2
2
2
3, 4
5
6
Terminal
Terminal
No.
color
1AB
BRN
2AB
RED
3AB
BLK
1AB
PUR
2AB
ORG
3AB
YEL
4AB
BLU
5AB
GRY
6AB
WHT
7AB
GRN
Specific
Attenuation
resistance
22Ω/km
56Ω/km
132Ω/km
20Ω/km
Size
2
1200m (depends on operation environment)
1.25sq
0.9sq
2
2
2
2
3, 4
6, 7
5
8
6
10, 12
7, 8
Flow tube drive output
BRN/RED, GRN/WHT, BLU/GRY, PUR/ORG/YEL shielded wires
bundled
Temperature input (inner)
Temperature input (outer)
Temperature input
Right position pickoff sensor input
Left position pickoff sensor input
Association-
recommended
3dB/km
5dB/km
8dB/km
8dB/km
Max. cable length
0.75sq
Remarks
2
FOUNDATION Fieldbus,
PROFIBUS PA Communication cable
2
6, 7
8
10, 12
Description