7.10.2 Separately mounted sensor unit and transmitter wiring

Interconnect cable (Max. 200m)
Barrier cover to be applied
in a hazardous area
CA00A, CA001, CA004
and CA006 to CA080
(T2, T3 and T4) are not
required.
Shield wires:Black
Sensor terminal box
NOTE 1. Do not fail to use dedicated interconnect cable.
2. Shield wire preparation
(1) Transmitter end :
As shown in the above figure, bundle shield wires colored in brown/red, green/white,
blue/grey, purple/yellow/orange, twist them, and cover the wires with a black tube. Then
connect only one wire to the terminal box (black) taking care to avoid potential contact
with the housing or conductive parts.
(2) Sensor end :
As shown in the figure, cover the brown/red shield wire with a black tube and connect it
to the terminal box taking care to avoid potential contact with the housing or conductive
parts. Clip all shield wires except brown/red as shown in the above figure.
    3. Recommended cable end treatment:
Use of a stick type crimp terminal is not necessary.
Cut off shield wires here except for the
shield wire over BRN and RED lines.
Shield
(Protected by black tube)
Brown
Red
Green
White
cut
Blue
Grey
cut
Purple
Yellow
Orange
cut
シール ド
(黒色チューブで保護)
カッ ト
カッ ト
9mm
カッ ト
Sensor terminal box
Brown
Red
Green
White
Blue
Grey
Purple
Yellow
Orange
Shield
(Protected by black tube)
Fig.7.9
L -- 740 -- 28 -- E
Transmitter
Interconnect cable
TypeU :  200m max.
TypeS Stainless steel tube type :  50m max.
TypeS Titanium tube type :  100m max.
TypeB :  5m max.
Transmitter terminal box
            