10.4 Explosionproof Specification
10.4.1 TIIS explosionproof
Applicable standard:
● Integral type
Converter symbol:
Detector symbol:
Ambient temp.:
Fluid Temperature:
Ex-proof applied temp.: +59℃
Power source:
Allowable voltage:
Communication:
NOTES: ※ If group of the detector is ⅡB, applicable gas for explosionproof configuration is limited
toⅡB as well.
※ If the temperature class of detector is T3, applicable explosive atmosphere is limited to up
to T3 as well.
● Separate type:
Converter symbol:
Detector Ambient Temp.: As shown on Detector Model Specification Table 1
Fluid Temperature:
Detector symbol:
Converter Ambient Temp.: -40℃ to +55℃
Power source:
Allowable voltage:
Communication:
Explanation about subject model codes
Model code: C①②③④-x⑤xxx-1⑥x-1⑦⑧x⑨x-x
Position
Meaning
Sensor Series
①
②③④
Nominal Size
Temperature
⑤
Classification
⑥
Temperature Class
Converter Installation
⑦
Structure
⑧
Power Source
⑨
Communication
Configuration
JNIOSH-TR-43-1 / JNIOSH-TR-43-2 / JNIOSH-TR-43-6
JNIOSH-TR-46-1 / JNIOSH-TR-46-2 / JNIOSH-TR-46-6
Ex d [ib] ⅡC T4X
Ex ib ⅡC T3 Gb, T4(CA series)
Ex ib ⅡC T3, T4(CB and CS series)
-40℃ to +55℃ ( -20℃ to +50℃ when connected with CS080 and CB040/050)
As shown on Detector Model Specification Table 1
AC220V 50/60Hz(100mA) , or DC30V(260mA)
AC250V 50/60Hz, DC250V
HART, Modbus PROFIBUS and FOUNDATION Fieldbus (FISCO)
Ex d [ib] ⅡC T6X
As shown on Detector Model Specification Table 1
Ex ib ⅡB / ⅡC T1, T2, T3, T4, T5(CA series)
Ex ib ⅡB T3, T4(CB, CS series)
AC220V 50/60Hz(100mA) , or DC30V(260mA)
AC250V 50/60Hz, DC250V
HART, Modbus PROFIBUS and FOUNDATION Fieldbus (FISCO)
Value
A
CA series
B
CB series
S
CS series
CA00A, CA001, CA003, CA006, CA010, CA015, CA025, CA040, CA050,
00A to 250
CA080, CA100, CA150, CA15H, CA200, CA20H and CA250
006 to 050
CB006, CB010, CB015, CB025, CB040 and CB050
010 to 080
CS010, CS015, CS025, CS040, CS050, CSR50 and CS080
1
Standard(-40℃ to +130℃)
2
Standard(+130℃ to +200℃)
3
High temp.(+200℃ to +350℃)
4
Low temp.(-200℃ to +50℃)
1
T1: Applicable sensor sizes CA025 to CA150
2
T2: Applicable sensor sizes CA003 to CA250
3 or 4
T3 or T4: All sensor sizes applicable
5
T5: Applicable sensor sizes CA025 to CA250
1
Integrally mounted models
2
Separately mounted models
1
20 to 30VDC
2
85 to 264VAC (Safety Rating: 100 to 240VAC) 50/60Hz
1
HART Communication (HART Protocol Version 7, Bell 202)
2
FOUNDATION Fieldbus H1 Communication (ITK Version 6)
3
PROFIBUS PA Communication (Profile Version 3.02)
4
Modbus Communication (RS-485 Modbus Protocol)
L -- 740 -- 28 -- E