7.6 Status Input Wiring

Status input appears across terminals S.I. (
Status input setup procedure appears in 9.7.4 Status input.
※ Status input will be invalid if FOUNDATION Fieldbus, PROFIBUS PA is selected as communication
interface.

7.7 Communication Line Wiring (option)

For communications (option), use terminals I/O. (
CAUTION: 1. Bell202 HART communications protocol does not use these terminals. It
uses analog output 1 terminal.
2. Other communication interfaces require different handling. Please refer to
the supplementary communication manuals.
FOUNDATION Fieldbus communication: "ALTImass series communication
manual for FOUNDATION Fieldbus L-740FF"
PROFIBUS PA communication: "ALTImass series communication manual
for PROFIBUS PA L-740PB"
Modbus communication: "ALTImass series communication manual for
Modbus L-740CM"

7.8 Recommended Cables Condition

Item
Label
L (+)
Power
N (-)
GND
A1 (+)
A1 (-)
A2 (+)
A2 (-)
P1 (+)
P1 (-)
Signal
P2 (+)
P2 (-)
S.I. (+)
S.I. (-)
S.O. (+)
S.O. (-)
I/O (+)
Communication
I/O (-)
External
ground
NOTE: ※1 Please select the cable size to be used with the number of signals.
※2 Depending on the number of output signals used, selection for the right cable material
must be made referring to the table on the next page.
0
) and S.I. (
Rating voltage/
allowable current
(at 30℃)
300V over, 2A over
100V over, 0.1A over
600V over, 40A over
).
) and I/O. (
).
Recommended condition
Cross-section
Solderless terminals
1.25sq to 2.0sq
R-type, 8.1mm less
AWG14 to 16
R-type, 7.2mm less
0.75sq to 2.0sq
AWG14 to 18
※1
Need no Screwless
terminal type
0.75sq
AWG18
Directly wiring or
4sq over
Solderless terminal
AWG12 over
(R-type, 8.1mm less)
Maximum
operating
temp.
Size: M4
Size: M3.5
60℃ over
※2