〈SENSOR (WAFER TYPE) 〉 〈SENSOR (FLANGE TYPE) 〉 Thank you for selecting the thermistor type OVAL VORTEX FLOWMETER. Every OVAL product is fabricated and shipped from our factory under stringent quality control. In order to maintain its design performance throughout the life of your meter, this manual offers the operator the necessary installation, operation and maintenance information.
D-160TS-7-E 1. BEFORE YOU BEGIN 1.1 Confirming the Specifications (1)Once the flowmeter is received, inspect its appearance and confirm that it is not damaged during transit. (2)Product code and specifications are indicated in the nameplate of the flowmeter. Make sure that information on the nameplate conforms to your particular specifications.
Read them carefully before you place the meter in service. [Example of Converter Nameplate] 3. GENERAL DESCRIPTION The OVAL VORTEX FLOWMETER is a vortex flowmeter with thermistor sensors, designed for gas measurement. Downstream of the bluff body, von Karman vortices form and shed alternately proportional to the rate of flow on either side of that triangular body placed perpendicular to the stream of flow.
D-160TS-7-E 4. PRINCIPLE OF OPERATION As a stream of fluid runs through the pipe, von Karman's vortices form and shed proportionally to the flowrate downstream of the bluff body located perpendicular to the stream of flow. Thermistor sensors in the sensor housing pick up these Karman vortices.
D-160TS-7-E 5. CONSTRUCTION (Component Names and Functions) (1)Sensor ① Meter body assembly It consists of a measuring pipe and a bluff body. As the metered fluid runs, Karman vortices form and shed downstream of the bluff body. ② Sensor assembly The assembly contains sensors to detect Karman vortices.
Accordingly, proper flow straightening measures must be taken when installing the OVAL VORTEX FLOWMETER. In applications where OVAL straightening devices (flow straightener, Honey vane, and downstream pipe) are used, a straight pipe section is not required unless otherwise specified.
Page 9
(3)Space Saving Arrangement If required straight pipe length is not available upstream of the vortex flowmeter due to existing restrictions on installation location, the OVAL Honey Vane S combined with a short pipe may be used for space saving. ● Honey Vane Outline Dimensions Unit:mm...
D-160TS-7-E 6.2 Pipes to be Used Upstream and downstream pipes adjacent to the flowmeter should be of the same internal diameter (ID) as the flowmeter. (The exclusive flow straightener, Honey Vane L, and downstream short pipe have the same ID as the flowmeter.) The table below shows the standard ID of the flowmeter.
D-160TS-7-E 6.5 Meter Installation To prevent troubles such as adverse effects on meter accuracy and gas leaks, the following should be taken into consideration when installing the meter: ① Make sure that the flow direction conforms to the arrow mark on the meter.
D-160TS-7-E 6.6 Lagging Work If temperature of the measured fluid exceeds 60℃ , even with explosionproof enclosure, the flowmeter must be insulated thermally (lagging). To facilitate maintenance and servicing, simple lagging (without mortar finish) is recommended around the flowmeter. Do not install lagging ...
D-160TS-7-E 6.8 Pulsation The performance of the flowmeter can be affected if pressure pulsation from instruments such as roots blower or compressor is significant. Minimize the pulsation pressure as much as possible by referring to the following equation: N< 22 ρ V...
D-160TS-7-E 〈Procedure〉 ① Turn off the power. ② Remove the cover clamp then remove the cover. A hex key (JIS B 4648, nominal size 3) is required. (Fig.6.12) ③ Separate the shield strip. A Phillips screwdriver Sensor Leads is required. (Fig.6.13) ④...
D-160TS-7-E 8. WIRING INSTRUCTIONS 8.1 Wiring Specification (1) Wiring for converter power source and output Do not use this conduit connection. Terminal Cover for Maintenance Fig. 8.1 The Rear of Converter (PA21) (2) Terminal label and description Label Description Remark POWER 24 to 32VDC DC power 24 to 32VDC...
Page 16
D-160TS-7-E (3) Wiring between converter and sensor Converter (PA21) SHIELD Sensor terminal box ★Sensor terminal box must be installed using intrinsically safe installation procedure. Fig. 8.2 ★ If there is wrong wiring in the connection between converter and detector, the converter may not start up normally even if the power supply is turned ON or an error alarm will be generated.
D-160TS-7-E 8.2 Wiring Considerations ① Use crimp terminals for M4 screw at the cable ends. ② This instrument uses the cable gland (pressure-tight packing) method of IEC harmonized standards for the external conductor entry of flameproof explosionproof configuration. Do not use cable glands other than the accompanying cable gland (not included with non-explosionproof products).
D-160TS-7-E 9.OPERATION Initiate operation in the following steps: ① Confirming the fluid specification Make sure that the fluid specification (composition, pressure, temperature, etc.) conforms to the meter specifications. ② Leak check Fill the meter with the fluid and check for any leak.
Error active: on, Alarm active: blink 10.2 Basic Operation 10.2.1 Setting Mode and Measuring Mode There are two modes available with the OVAL VORTEX FLOWMETER: Measuring Mode and Setting Mode. 「Measuring Mode」 : Appears after powering on or exiting Setting Mode explained in section 12.
D-160TS-7-E 10.2.2 Key Operation Key operations of OVAL VORTEX FLOWMETER are performed by holding the accompanying switching magnet (Fig.7.1) close to magnetic switch areas [SEL key] and [ENT key]. Magnet sensors detect the switching magnet and turn the key input ON.
D-160TS-7-E 11. MEASURING MODE 11.1 Measuring Mode Display Measuring Mode appears after powering on or exiting Setting Mode explained in section 12, showing the display as figure on the right. The upper display shows % flow rate. This display can be switched between % flow rate and MODE by key operation.
D-160TS-7-E 11.3 Switching Display Display contents can be switched on Measuring Mode. To do so, use [ENT] key to focus (blinking) on the upper display, then use [SEL] key input to change the display contents. Focusing turns off if no key input is made within 10 seconds.
The default password is "0000" and the password function is "disabled" as factory setting. When enabling the password function, please be careful about handling of the password. (In case you forget the password, contact the nearest OVAL sales/service office or representative in your area.) Measuring Mode/Setting Mode switching operation...
D-160TS-7-E 12.2 Setting Mode Menu Operation Use [SEL] and [ENT Hold] to navigate between items in Setting Mode. At each item, "level code" is displayed for 2 seconds to indicate the setting item. See section 13. MENU TREE for details of each setting item.
D-160TS-7-E 12.3 Parameter Change Parameter can be changed by the following procedure: Select the desired item to display the current setting of the parameter on the bottom display. Perform [ENT Hold] to activate parameter editing mode. CAUTION: To prevent unexpected erroneous operation, perform setting changes at zero flow condition as a general rule.
D-160TS-7-E 12.3.2 Numeric Parameter Setting (e.g. Hi alarm) Once parameter editing mode is active, the leftmost digit of the parameter starts blinking ("focused"). [SEL] to change the value of the focused digit and [ENT] to shift the focused digit to the right.
D-160TS-7-E 12.3.3 How to read exponent The exponent is used as [Significant figure × Exponent (n power of 10)]. For example, to enter [123.45], which can be written as 1.2345 × 10 , enter 1.2345E2. (10 =100) To set negative exponent, for example [0.012345] which can be written as 1.2345 × 10 , enter 1.2345-2.
D-160TS-7-E 13. MENU TREE [SEL] [SEL Hold] [ENT Hold] Transition after entering password 【Upper LCD】 Mode selection ※1 Operate while display is blinking. % flow rate **% ※2 Displayed only if password function is valid. display % ※1 ※3 Not displayed if [AL.Fun] is [non]. modE Setting Mode ※1 Main parameter PAS.wd Enter password Sub-parameter ※2 Password setting Password selection Pw.oPt Pw.oPt 00−00 00−01 Password setting Pw.SEt 00−02 Sub-parameter Flow rate setting Full scale flow rate FLow FL.FSC 01−00...
Page 29
D-160TS-7-E Parameter description Default Password function enable/disable selection. When "ON" is selected, password input will be Off required before entering the setting menu screen to prevent unwanted parameter changes. Password setting. To enable the set password, password function must be "ON". Be careful not to 0000 forget the password. Parameter description Default Full scale (max. measuring flow rate) of % flow rate can be changed. Varies with ※Unit: m /h (standard setting) customer spec. Min. measuring flow rate can be changed. Flow rate below this setting will not be measured. Effective for Varies with the prevention of erroneous output due to zero flow fluctuation (noise). ※Unit: m /h (standard setting) customer spec. Varies with Meter factor (L/Pulse) setting. customer spec. Parameter description Default Status output logic setting. OPEn See section 14. STATUS OUTPUT for detail Function assignment setting of status output. See section 14. STATUS OUTPUT for detail Pulse width setting. ※Unit: msec Parameter description Default Function assignment setting of flow alarm. See section 15. HIGH/LOW ALARM for detail High alarm setting. Alarm output is generated when flow rate is above this setting. Varies with customer spec. ※Unit: m /h (standard setting)
Page 31
D-160TS-7-E Parameter description Frequency setting of simulated pulse. Simulated pulse output stops when the number of output reaches this count setting. If set at [0], simulated pulse output will not stop automatically. [ENT Hold] to start simulated pulse output. Parameter description Parameter for OVAL service personnel. Displays circuit voltage inside the converter. Displays circuit voltage inside the converter. Displays circuit voltage inside the converter. Displays circuit voltage inside the converter. Parameter for OVAL service personnel. Parameter for OVAL service personnel. Displays the resistance value of Sensor 1. Displays the resistance value of Sensor 2. Displays the voltage value of Sensor 1. Displays the voltage value of Sensor 2. [ENT Hold] to turn on every segment of LED. [SEL Hold] to exit. Parameter description Parameter for OVAL service personnel. Parameter for OVAL service personnel. Parameter for OVAL service personnel. Parameter for OVAL service personnel. Parameter description Parameter for OVAL service personnel. Parameter description Displays the voltage value of Sensor 1. Displays the voltage value of Sensor 2. See the parameter list for setting ranges and selectable items.
D-160TS-7-E 14. STATUS OUTPUT This flowmeter is capable of status output of error/alarm condition. Status output related setting can be done at "Out Pt" sub-menu of setting menu. Status output is of open drain output (equivalent of open collector). ■ Status output assignment A function can be assigned to status output.
D-160TS-7-E 15. HIGH/LOW ALARM This function activates an alarm when flow rate reading is out of the set range. High/Low alarm can be enabled by assigning the function to [AL.Fun]. To perform settings related to high/low alarm, go to [ALArm] sub-menu.
D-160TS-7-E 16. LOOPTEST (OUTPUT SIMULATION) Looptest generates pulse output as simulation in order to confirm the connection between the flowmeter and an external instrument. Looptest can be executed from sub-menu [Fix.PL] under Setting Mode [mAint]. Output frequency and output pulse count can be set at any value with in the ranges of 1.0 to 2000.0Hz, and 0 to 99999999, respectively.
D-160TS-7-E 17.PARAMETER LIST Items: Name: Parameter name Range: Selectable data range Unit: Parameter unit Display: R = display only, W = both display and setting available Device information Name Description / Range Unit Display Tag number setting / 8 characters —...
Page 36
D-160TS-7-E Status output Name Description / Range Unit Display Condition selection of status output. Selection item Description Normal Open Status terminals are normally open. Status output mode — ( ) Normal Close Status terminals are normally closed. ( ) ( ) represents LCD display.
Page 37
D-160TS-7-E Flow rate setting Name Description / Range Unit Display If no flow pulse input is detected during the set duration Sampling time — (second), instant flow rate reads "0". / 1 to 999 If instant flow rate varies considerably, set larger value to reduce Sample cycle number —...
D-160TS-7-E 19. MAINTENANCE This flowmeter is manufactured and inspected under stringent quality control program before leaving the factory. As long as the flowmeter is used under proper conditions, its performance will remain stable. In cases of trouble, check the items listed in the below table.
Page 40
D-160TS-7-E (2)Insulation Resistance Measurement Remove sensor leads (2 white, 1 red (black)) inside the terminal box on the meter side and make a resistance measurement against the housing. Rating: Greater than 100M Ω at 25V DC across the sensor leads grouped ...
D-160TS-7-E ④ Take off four hex socket head bolts (213) and remove the assembly above the adaptor (209). The sensor unit (201) is mounted on the adaptor with the hex socket head bolt (214). Fig. 19.2 Sensor unit ⑤ A pair of thermistor sensors are molded at the tip of the sensor unit. Visually examine them for contamination.
Page 42
D-160TS-7-E Voltage measurement Name Measurement points Standard Remarks Converter output terminal If ① is missing, check Converter block ① 22.0 to 34.0V receiving instrument power +・・・・・・POWER supply voltage supply. -・・・・・・COMMON ※ Use a digital voltmeter or tester for measurement. Pulse waveform observation...
D-160TS-7-E 20.ASSEMBLY DRAWINGS AND PARTS LIST (1)Meter body assembly drawings Wafer type 20mm (3/4") Wafer type 25mm (1") to 150mm (6") Flange type 200mm (8") to 500mm (20") Fig. 20.1 Meter body ● Meter body parts list Part Name...
Page 44
D-160TS-7-E (2)Sensor assembly drawings Fig. 20.2 Sensor assembly ● Sensor parts list Part Name Q'ty Remarks ▲ 201 Sensor Unit Sensor Housing Block Valve ▲ 204 Dust filter Dust filter housing Mist Release Screw Adaptor Hex thin nut Machine screw M4×6...
D-160TS-7-E 21. GENERAL SPECIFICATIONS (1)Standard Meter Body Item Item Description Body style Wafer Flange Nominal size (mm) 20, 25, 32, 50, 80, 100, 150 200, 250, 300 400, 500 Meter body SUS304 STPG370 SUS304TP STPY400 SUS304TP SS400 Material Flange —...
Page 46
D-160TS-7-E (2)Converter Item Description Model PA21 converter Configuration Separately mounted Power source 24 to 32VDC Power consumption 32V 40mA or less (24V 54mA or less) Non-explosionproof −20 to +60℃ (no condensation) Ambient temperature Explosionproof −20 to +55℃ (no condensation) Finish Body: Munsell 10B8/4, Cover: Munsell 2.5PB4/10...
Page 47
NOTE: 1. Flow ranges listed in above table is calculated based on temperature 20℃ and viscosity 0.017mPa•s. 2. If it is necessary to determine the minimum flow rate precisely, contact OVAL. How to Determine Minimum Flow Rate Example 1 A 200mm (8″ ) size meter is to be used for air having a pressure of 0.74MPa [gauge] at 20℃ . Find the minimum flow rate.
Page 48
D-160TS-7-E (4)Performance Characteristics ● Pressure Loss ● Nominal sizes 20 to 32mm ● Nominal sizes 50 to 500mm 20 30 Flow rate Qm /h [actual] Flow rate Qm /h [actual] Fig. 21.1 ○ How to Determine Pressure Losses C× ρ...
D-160TS-7-E 22. OUTLINE DIMENSIONS (Standard type) (1)Meter body NOTE: Outline dimensions of special or regulation-compliant products may be different. Please refer to the delivery specification. Unit in mm Wafer type 20mm (3/4″ ) Wafer type 25mm (1″ ) to 150mm (6″ ) ●...
Page 50
D-160TS-7-E (2)Converter Unit in mm 61.5 171.5 Conduit Connection Conduit Connection G3/4 G3/4 Fig. 22.2...
D-160TS-7-E 23. EXPLOSIONPROOF SPECIFICATION 23.1 Converter Explosionproof model code: PA21-2 Explosionproof symbol: Ex d e Ⅱ C T6 Ambient temperature: -20℃ to +55℃ Rated power: DC32V Current DC40mA, Output signal pulse/Status signal DC32V 50mA 24.1 Explosionproof Label 製造者名称 株式会社オーバル 横浜事業所...
D-160TS-7-E 23.3 Explosionproof applied temperature range (for explosionproof models) Explosionproof applied temperature range of the instrument is -20℃ to +72℃ at the part indicated below. To satisfy the requirements, make sure to use the instrument within the suggested range of fluid and ambient temperature shown below.
Main code ● ① ② ③ Model ⑯ Regulations V F W OVAL VORTEX FLOWMETER Wafer type (Nominal Size: 20 to 150mm) 0 Standard No applicable law and regulations OVAL VORTEX FLOWMETER Wafer type, spigot joint type High Pressure Gas Safety Act ※...
Page 54
D-160TS-7-E Converter (Power supply) Converter configuration Regulations Display Explosion-proof Pulse Process connection Communication interface Major Parts Material Version code Temp. category Sensor configuration Fluid category Sensor type Nominal Size Accompanied cable length Model Special ① ② ③ ④ ⑤ ⑥...
Page 55
The new product code has been implemented since April 2017. Therefore, the product code explanation of the old product code will not be updated after April 2017. Contact OVAL if you wish to order with the old product code for reasons such as type approval. Product Code...
Page 56
D-160TS-6N-E 2021.05 Revised△ 2016.04 Released All specifications are subject to change without notice for improvement. D-160TS-7-E (1)...