Inspection Items
Periodically inspect the following items:
Item
Environmental
Is the ambient operating temperature
conditions
(temperature inside the control box)
appropriate?
Is ambient operating humidity (humidity
inside the control box) appropriate?
Has dust collected on the Unit?
Mounting
Is the Unit securely mounted?
conditions
Are the plugs inserted completely?
Are the cables intact?
Have at least one spare Unit on hand for quick recovery in case of a failure.
Consumable Parts
Battery set: Model C200H-BAT09
The life of the battery is 5 years at 25 C. If the battery is used at a higher temperature, its life is shortened.
Assignment of the battery error flag differs depending on the message output mode, as follows, where n =
100 + 10 x unit no:
In sentence mode: word n+5 bit 05
In phrase combination mode: word n+9 bit 05
When the ERR indicator is lit due to a low battery, replace the battery with a new one within 1 week.
Replacing the Battery
1, 2, 3... 1.
Note
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Appendix A
Inspection and Maintenance
Particulars
Turn OFF the power. When the power is OFF originally, turn the power
ON to supply power to the Unit for at least 1 minute and then turn the
power OFF.
2.
Remove the protective cover on the battery compartment of the Voice
Unit by pushing it downward (see Fig. 1).
3.
Pull out the battery with the connector, and replace the battery. Com-
plete this procedure within 5 minutes (see Fig. 2).
4.
When mounting the new battery in the compartment, make sure that the
cable of the battery fits correctly in the compartment.
5.
Attach the protective cover by pushing it up, until the cover catch clicks
into the hole above the compartment (see Fig. 2).
Do not short-circuit the positive and negative poles of the battery or throw a
used battery into a fire: doing so may cause the internal liquid of the battery
to leak out, or the battery to catch fire or even explode.
Normal Operating Criteria
0 to 55 C
35 to 85% (without condensation)
The Unit must be free of dust.
The Unit must not be loose.
The plugs must be inserted completely.
The appearance must be normal.
Remarks
Thermometer
Hygrometer
Visual
inspection
Periodic
inspection
Periodic
inspection
Visual
inspection
87