Loading The Hw Config To Ncu - Siemens SINUMERIK 840D sl Commissioning Manual

Cnc commissioning: nc, plc, drive
Hide thumbs Also See for SINUMERIK 840D sl:
Table of Contents

Advertisement

PLC commissioning
5.8 Configuring a network (NetPro) for PG/PC
5. Now assign the remaining configured PROFIBUS interfaces. From those interfaces
assigned, one must be marked as "active".
6. Select "Ethernet interface" in the "Assigned" field and mark the field next to it as "active".
7. Click "OK" to end the "Properties - PG/PC" dialog.
In NetPro, the PG/PC interface declared as "active" has a yellow background.
8. Select "Save and compile → Save and check all" and confirm the process with "OK".
The next described operating sequence explains how to load this hardware configuration to the
NCU.
5.8.4

Loading the HW config to NCU

Introduction
The newly created network configuration PG/PC must be introduced to the NCU.
You have established a connection to the Ethernet interface (X120 or X127) and you now load
this configuration from the PG/PC to the NCU.
100
CNC Commissioning: NC, PLC, Drive
Commissioning Manual, 12/2019, A5E48312804B AA