Test Operation Of The Servo Motor Alone In Test Operation Mode - Mitsubishi Electric MELSERVO-J5 Series User Manual

Ac servo system
Hide thumbs Also See for MELSERVO-J5 Series:
Table of Contents

Advertisement

Test operation of the servo motor alone in test operation mode

• If the servo motor operates in an unintended manner, stop the servo motor with EM2 (Forced stop 2).
Check that the servo amplifier and servo motor operate normally. With the servo motor disconnected from the machine, use
the test operation mode and check whether the servo motor operates correctly. This section describes how to check the servo
motor operation in the JOG operation. The test operation also includes the positioning operation and program operation.
Page 47 Test operation
In the linear servo motor control mode, the JOG operation cannot be performed. Check the motor operation by using the
positioning operation or by other means.
Page 48 Motor driving by test operation
1.
Turn off the power.
2.
Turn "ON (up)" the test operation select switch (SW3-1).
RUN
MS
ERR
NS
SFTY
3.
Turn on the power supply of the servo amplifier. When initialization is completed, the display shows as follows.
Test operation status display
The display of a 1-axis servo amplifier is shown as an example.
4.
Open the "JOG Mode" screen of MR Configurator2.
ON
1
2
Set SW3-1 to "ON (up)".
4.1 Turning on servo amplifier for the first time
4
4 STARTUP