Bosch Rexroth IndraMotion MLD Series Applications Manual page 203

Table of Contents

Advertisement

DOK-INDRV*-MLD3-**VRS*-AP02-EN-P
Rexroth IndraDrive Rexroth IndraMotion MLD (2G) as of MPx-18
Importing an archived MLD project
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Fig. 7-28:
Summary of the Restored MLD Project
Possible changes in the enabling of functional packages only take
effect at the next restart of the drive.
13. If the firmware version in the restored MLD project is the same as the
firmware version of the connected drive, you can go online with the
drive.
The following steps describe what to do to restore an archived MLD project.
Make sure that the same or a higher version of IndraWorks MLD as used
when the archive was created is installed on the PC with which the archived
MLD project is restored.
When the archived MLD project is to be used in a CCD group, the CCD
group has to be commissioned before the MLD project is restored:
1. Set the following parameters according to configuration of installation:
CCD slave: Drive address (P-0-4089.0.3) and, if necessary, selec‐
tion of functional packages (P-0-2003).
CCD master: If necessary, selection of functional packages
(P-0-2003) and setting TCP/IP communication (P-0-1531 to
P-0-1533).
Changes to enabled functional packages and the TCP/IP commu‐
nication settings only take effect on the next restart of the drive.
2. In IndraWorks MLD, set desired type of communication (serial or
TCP/IP) and go online with the drive (CCD master). Switch the drive on‐
line via "Switch online" in the context menu of the drive (right-click the
drive branch in the project tree).
Bosch Rexroth AG
Notes on commissioning and application
201/267