Bosch Rexroth IndraMotion MLD Series Applications Manual page 161

Table of Contents

Advertisement

DOK-INDRV*-MLD3-**VRS*-AP02-EN-P
Rexroth IndraDrive Rexroth IndraMotion MLD (2G) as of MPx-18
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Fig. 6-33:
Selecting the "communication driver" "BR_WS"
5. Use the context menu of the driver that was just added to call the "Prop‐
erties" dialog.
Fig. 6-34:
Calling the "Properties" dialog of "BR_WS"
6. Make the following settings in the "Properties" dialog of "BR_WS":
"Serial encapsulation": "None"
"Timeout in ms": Enter a timer monitor for the communication con‐
nection. Recommended value for a communication connection to
the drive controller: ≥1000 ms.
"IP address": TCP/IP address of target control unit
"No connection check (CE)": "0" (the communication connection
should also be monitored in devices designated CE).
Bosch Rexroth AG
Visualization and engineering interfaces
159/267

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rexroth indramotion mld-sRexroth indramotion mld-m

Table of Contents