Alarm Procedures
c.
After determining the port is active, verify the signal source to the traffic card reporting the alarm.
Step 2
If traffic is being affected, delete and recreate the circuit.
Step 3
Caution
Check the far-end OC-N card that provides STS payload to the XTC card.
Step 4
Verify the cross-connect between the OC-N card and the XTC card.
Step 5
Step 6
Clean the far-end optical fiber:
a.
b.
Step 7
Replace the OC-N/XTC cards.
Note

14.4.95 PLM-V

A VT-payload label mismatch (PLM-V) alarm indicates that the content of the V5 byte in the SONET
overhead is inconsistent or invalid. This alarm occurs when ONS nodes interoperate with equipment that
performs bit-synchronous mapping for DS-1. ONS nodes use asynchronous mapping.
Procedure: Clear the PLM-V Alarm on the XTC-14 or XTC-28-3 Card
Verify that your signal source matches the signal allowed by the traffic card. For example, the traffic card
Step 1
does not allow VT6 or VT9 mapping.
Verify that the SONET VT path originator is sending the correct VT label value. You can find the
Step 2
SONET VT path originator using circuit provisioning steps.

14.4.96 PRC-DUPID

The procedural error duplicate node ID (PRC-DUPID) alarm indicates that two identical node IDs exist
in the same ring. The ONS 15327 requires each node in the ring to have a unique node ID.
Cisco ONS 15327 User Documentation, R3.3
14-68
If the State column lists the port as INCOMPLETE, wait 10 minutes for the ONS 15327 to fully
initialize. If INCOMPLETE does not change after full initialization, login to
http://www.cisco.com/TAC for more information or call the Cisco Technical Assistance Center to
report a service-affecting problem (1-800-553-2447).
Deleting a circuit may affect traffic.
Clean the fiber according to local site practice.
If no local practice exists, use a CLETOP Real-Type or equivalent fiber-optic cleaner and follow the
instructions accompanying the product.
When you replace a card with an identical type of card, you do not need to make any changes to
the database.
Minor, Service-Affecting
Major, Service-Affecting
Chapter 14
Alarm Troubleshooting
June 2002