Dnp Point Mapping; Dnp Point Maps - GE Multilin EPM 6000 Instruction Manual

Multi-function power meter
Hide thumbs Also See for Multilin EPM 6000:
Table of Contents

Advertisement

5.2

DNP Point Mapping

5.2.1

DNP Point Maps

Object
Var
Point
Binary output states (Read via Class 0 only)
0
Reset energy counters
10
2
1
Change to Modbus RTU protocol
Control Relay Outputs
0
Reset energy counters
12
1
1
Change to Modbus RTU protocol
Binary Counters (Primary; read via Class 0 only)
0
Positive watt-hours
1
Negative watt-hours
20
4
2
Positive var-hours
3
Negative var-hours
4
Total VA-hours
Analog Inputs (Secondary; read via Class 0 only)
30
5
0
Meter health
1
Voltage A-N
2
Voltage B-N
3
Voltage C-N
4
Phase voltage A-B
5
Phase voltage B-C
6
Phase voltage C-A
7
Phase A current
8
Phase B current
9
Phase C current
10
Total three-phase real power
11
Total three-phase reactive power
12
Total three-phase apparent power
13
Total three-phase power factor
14
Frequency
5–10
The DNP point mappings (DNP-11 to DNP-22) for the EPM 6000 Power Metering System
shows the client-server relationship in GE Multilin's use of the DNP protocol. The notes are
listed after the table.
Table 5–1: DNP Point Mapping (Sheet 1 of 2)
Description
Format
Range/units
BYTE
0
BYTE
0
N/A
N/A
N/A
N/A
UINT32
0 to 99999999 Wh
UINT32
0 to 99999999 Wh
UINT32
0 to 99999999 varh
UINT32
0 to 99999999 varh
UINT32
0 to 99999999 VAh
SINT16
0 or 1
SINT16
0 to 32767 V
SINT16
0 to 32767 V
SINT16
0 to 32767 V
SINT16
0 to 32767 V
SINT16
0 to 32767 V
SINT16
0 to 32767 V
SINT16
0 to 32767 A
SINT16
0 to 32767 A
SINT16
0 to 32767 A
SINT16
–32768 to +32767 W
SINT16
–32768 to +32767 var
SINT16
0 to 32767 VA
SINT16
–1000 to 1000
SINT16
0 to 9999 Hz
EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE
CHAPTER 5: COMMUNICATIONS
Multiplier
Comments
N/A
N/A
N/A
See note 1
N/A
See note 2
See note 3
See note 4
See note 3
See note 4
See note 3
See note 4
See note 3
See note 4
See note 3
See note 4
N/A
0 = OK
(150/32768)
See note 5
(150/32768)
See note 5
(150/32768)
See note 5
(300/32768)
See note 6
(300/32768)
See note 6
(300/32768)
See note 6
(10/32768)
See note 7
(10/32768)
See note 7
(10/32768)
See note 7
(4500/32768)
(4500/32768)
(4500/32768)
0.001
0.01

Hide quick links:

Advertisement

Table of Contents
loading