Binary Input / Binary Input Change Point List - GE Multilin PQM Instruction Manual

Power quality meter
Table of Contents

Advertisement

CHAPTER 8: DNP COMMUNICATIONS
8.1.5
Binary Input /
Binary Input
Change Point
List
PQM POWER QUALITY METER – INSTRUCTION MANUAL
Courtesy of NationalSwitchgear.com
Table 8–2: Point List for Binary Input (Object 01) / Binary Input Change (Object 02)
INDEX
DESCRIPTION
0
Alarm condition(s) active
1
Clock not set
2
Clock drifting
3
Internal error: ADC reference out of range
4
Internal error: HC705 processor not responding
5
Internal error: switch input circuit fault
*
PQM (display) option installed
6
7*
T20 (4-20 mA transducer) option installed
8*
T1 (0-1 mA transducer) option installed
9*
C (control) option installed
10*
A (power analysis) option installed
11
Switch A closed
12
Switch B closed
13
Switch C closed
14
Switch D closed
15
Alarm relay energized
16
Auxiliary relay 1 energized
17
Auxiliary relay 2 energized
18
Auxiliary relay 3 energized
19
Aux 1 relay LED active
20
Aux 2 relay LED active
21
Aux 3 relay LED active
22
Alarm LED active
23
Program LED active
24
Simulation LED active
25
Alarm relay LED active
26
Self test LED active
27
28
29
30
31
32
33
34
35
Alarm active: phase undercurrent
36
Alarm active: phase overcurrent
37
Alarm active: neutral overcurrent
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
DNP 3.0 PROTOCOL
EVENT CLASS
NOTES
ASSIGNED TO
Class 1
Class 1
Note 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
Class 1
-----
-----
-----
-----
-----
-----
-----
-----
Class 1
Class 1
Class 1
8–7