SPECIFICATIONS
This chapter explains general and performance specifications of CC-Link IE Field Network board.
3.1

General Specifications

General specifications of CC-Link IE Field Network board are shown below.
Item
Operating ambient temperature
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Shock resistance
Operating atmosphere
*1
Operating altitude
Installation location
*2
Overvoltage category
*3
Pollution degree
*1 Do not use or store the board under the environment where the atmospheric pressure is higher than the one at the altitude of 0 m. Doing
so may cause a malfunction.
*2 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
*3 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used.
Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected
occasionally.
The general specifications both CC-Link IE Field Network board and a personal computer must be satisfied
after installation.
Specification
0 to 55
-25 to 75
5 to 95% RH, non-condensing
Compliant
Frequency
with JIS B
3502 and IEC
Under
5 to 8.4 Hz
61131-2
intermittent
8.4 to 150 Hz
vibration
Under
5 to 8.4 Hz
continuous
8.4 to 150 Hz
vibration
Compliant with JIS B 3502 and IEC 61131-2 (147 m/, 3 times each in X, Y, and Z directions)
No corrosive gases
0 to 2000 m
Inside a control panel
II or less
2 or less
Constant
Half amplitude
acceleration
3.5 mm
9.8 m/
1.75 mm
4.9 m/
3 SPECIFICATIONS
3.1 General Specifications
3
Sweep count
10 times each in X, Y,
and Z directions
35

Hide quick links: