Error Invalid Station And Temporary Error Invalid Station Setting Function - Mitsubishi Electric MELSEC SW1DNC-CCIEF-B User Manual

Cc-link ie field network interface board
Table of Contents

Advertisement

5.6
Error Invalid Station and Temporary Error Invalid
Station Setting Function
When a slave station is set as an error invalid station, even if it is disconnected from the network during data link, the master
station will not detect it as error station.
Furthermore, by the temporary error invalid station setting function, a slave station can be temporarily set as an error invalid
station.
Error invalid station setting
A slave station can be set as an error invalid station in "Network Configuration Setting".(Page 101 Network configuration
setting)
Master station
(Station No.0)
Network Configuration Setting
Temporary error invalid station
This function is useful for various operations such as replacing a slave station during a data link by temporarily setting it as an
error invalid station.
For setting temporary error invalid station, refer to the following section.
Page 135 Enable/Disable ignore station errors
5 FUNCTIONS
76

5.6 Error Invalid Station and Temporary Error Invalid Station Setting Function

Slave station
Slave station
(Station No.1)
(Station No.2)
Slave station
(Station No.3)
No data link error will be detected on
this station even in the case of
Error invalid station
an error or power OFF.
Select "Invalid Station".