Appendix 13Behavior When Personal Computer Enters Power Save Mode Or Fast Startup; Behavior When The Personal Computer Enters The Power Save Mode (Hibernate, Sleep); Behavior When Fast Startup Function Is Enabled - Mitsubishi Electric MELSEC SW1DNC-CCIEF-B User Manual

Cc-link ie field network interface board
Table of Contents

Advertisement

Appendix 13
CC-Link IE Field Network board does not support the power save mode (hibernate, sleep) and fast startup. The following
explains the behavior of the personal computer when the personal computer enters each mode.
Behavior when the personal computer enters the power save
mode (hibernate, sleep)
Target operating system
The following operating systems have the power save mode (hibernation, sleep)
• Windows 10, Windows Server 2016, Windows Server 2019
• Windows 8.1, Windows Server 2012 R2
• Windows 8, Windows Server 2012
• Windows 7, Windows Server 2008 R2
Behavior when entering the hibernation mode/sleep mode
The following explains the behavior of the board when the power save mode (hibernate, sleep) is entered on the personal
computer.
• The CC-Link IE Field Network board stops its operation and is disconnected from the network.
• The board is not reconnected even after the personal computer returns from the power save mode (hibernate, sleep).
• After the personal computer returns from the power save mode (hibernate, sleep), "-28141(9213H) : System sleep error"
occurs when accessing CC-Link IE Field Network board from the CC IE Field utility or an application program, which
includes MELSEC data link library function.
Corrective action
When the personal computer is set to enter the power save mode (hibernate, sleep), the setting is changed by
MELSECPowerManager.
For details of MELSECPowerManager, refer to the following section.
Page 231 MELSECPowerManager

Behavior when fast startup function is enabled

Target operating system
The following operating systems have the fast startup function.
• Windows 10, Windows Server 2016, Windows Server 2019
• Windows 8.1, Windows Server 2012 R2
• Windows 8, Windows Server 2012
Behavior when the fast startup function is enabled
The following explains the behavior of the board when the fast startup function is enabled.
• The board is not reconnected even after the fast startup.
• After the fast startup, "-28141(9213H) : System sleep error" occurs when accessing CC-Link IE Field Network board from
the CC IE Field utility or an application program, which includes MELSEC data link library function.
Corrective action
When the fast startup function is enabled on the personal computer, the setting is changed by MELSECPowerManager.
For details of MELSECPowerManager, refer to the following section.
Page 231 MELSECPowerManager
APPX
230
Appendix 13 Behavior When Personal Computer Enters Power Save Mode or Fast Startup
Behavior When Personal Computer
Enters Power Save Mode or Fast Startup

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec q80bd-j71gf11-t2Melsec q81bd-j71gf11-t2

Table of Contents