Network configuration
CC-Link IE Field Network configuration and status of each station are displayed.
When the status of each station is not displayed, check if master stations or station numbers are not duplicated.
Window
(1)
(2)
(3)
Displayed items
No.
Item
(1)
Connected Station
(2)
Network type
Station No.
(3)
Icon
(4)
Port
(5)
Divergence
■Icon
By clicking an icon, the station is set as a selected station and details are displayed in "Selected Station Communication
Status Monitor".
(A station with an error, such as master station duplication or station number duplication, details are not displayed as a
selected station even by clicking the icon. In such case, execute the board diagnostics on the error station, and determine the
error cause. When the error station is a module, determine the error cause using the system monitor function of GX Works2.)
Use the right and left arrow keys to move the focus and press the or key to confirm the selected station.
The same functions as the functions of "Operation Test" and "Information Confirmation/Set" can be executed from the menus
displayed by right-clicking the icon.
The content of the displayed icons can be confirmed with the [Legends] button. (Page 123 Legends)
13 DIAGNOSING BOARD STATUS
124
13.2 Diagnosing CC-Link IE Field Network
(4)
Description
Indicates a station connected to the utility (own station).
Displays a network type and station number. "?" is displayed when a station number has not been set.
When the background of the characters is colored, setting such as reserved station specification has been
configured to the relevant station.
Displays a module type and station status.
Displays a port to which an Ethernet cable is connected.
A branch of star topology configured by using a network device such as a hub.
(5)