Functional comparison
■Added functions
The following are the functions added in the CC-Link IE Field Network.
Function
Cyclic transmission
Transient transmission
CC-Link IE Field
Network diagnostics
Other
■Modified functions
The following are the functions modified in the CC-Link IE Field Network board.
Function
Slave station cut-off function
Standby master function
Data link status setting for error occurrence of
CC-Link module master station CPU
APPX
220
Appendix 7 Comparison of CC-Link and CC-Link IE Field Network
Description
Mode selection for cyclic
This mode can be selected for optimizing the performance of
transmission
cyclic transmission based on the frequencies of cyclic
transmission and transient transmission. The mode can be
selected from "Online (Normal mode)" and "Online (High-
speed mode)".
Seamless transmission with
Setting the routing parameters beforehand also enables
different networks
transient transmission to stations in different networks.
Communication is also possible with the CC-Link IE Controller
Network, and MELSECNET/H.
Network configuration
The network configuration can be checked by the CC-Link IE
display
Field Network diagnostics of CC-Link IE Field Utility.
Loop test
Check the network circuit status and parameter setting status
of each station.
Cable test
Check the connection status of the Ethernet cable.
Communication test
Check whether the communication path for transient
transmission from the own station to the target station is
correct.
Network event history
The history of events that occurred in the own station and on
the network is displayed. For the master station, the event
history of the entire network can be displayed, and so it can be
used for troubleshooting at network start-up.
Reserved station temporary
Reserved stations can be temporarily disabled without
disablement
changing parameters.
Notes during replacement
When the CC-Link IE Field Network is connected in a line topology, stations after the disconnected station
become data link faulty stations. To prevent disconnection of normal stations, connect the CC-Link IE Field
Network in a star topology. (Page 21 Network configuration)
No standby master function is available in the CC-Link IE Field Network board.
The setting is fixed to "Continue" for CC-Link IE Field Network.
Reference
Page 100 Network type and mode
Page 218 Differences in Cyclic
Transmission Modes
Page 69 Communication with
different networks
Page 118 Diagnosing CC-Link IE
Field Network
Page 54 Loop test
Page 55 Cable test
Page 56 Communication test
Page 132 Network event history
Page 75 Reserved Station
Specification and Reserved
Station Function Disable Function
Page 134 Reserved station
function enable

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec q80bd-j71gf11-t2Melsec q81bd-j71gf11-t2

Table of Contents