Mitsubishi Electric MELSEC SW1DNC-CCIEF-B User Manual page 206

Cc-link ie field network interface board
Table of Contents

Advertisement

Number
Name
SW0071
Loopback station
number 2
SW0074
PORT1 cable
disconnection
detection count
SW0075
PORT1 receive error
detection count
SW0076
PORT1 total number
of received data
(lower 1 word)
SW0077
PORT1 total number
of received data
(upper 1 word)
SW007A
Event count
SW007C
PORT2 cable
disconnection
detection count
SW007D
PORT2 receive error
detection count
SW007E
PORT2 total number
of received data
(lower 1 word)
SW007F
PORT2 total number
of received data
(upper 1 word)
SW0080 to
Execution status
SW009F
(REMFR/REMTO)
APPX
204
Appendix 4 Link Special Register (SW) List
Description
Stores the number of the station where loopback is being performed. The other
loopback station number can be checked by Loopback station number 1 (SW0070).
• 0: No loopback stations
• 1 to 120: Slave station
• 125: Master station
• 255: Station number not set
If a station whose station number duplicates is performing loopback, this register
stores the duplicated number.
(Conditions)
This is enabled when Baton pass status (own station) (SB0047) is OFF and Network
configuration mismatch occurrence status (SB0098) is OFF.
Stores the (cumulative) count that was detected for cable disconnections at the
PORT1.
When Clear communication error count (SB0006) is turned ON, the stored count is
cleared.
Stores the (cumulative) count that error data was received at the PORT1.
The count stores only error data that is not transmitted to all stations.
When Clear communication error count (SB0006) is turned ON, the stored count is
cleared.
(Conditions)
This is enabled when the Mode status (SW0043) is 0 or 1. (during online)
Stores the (cumulative) count that error data was received at the PORT1.
When Clear communication error count (SB0006) is turned ON, the stored count is
cleared.
(Conditions)
This is enabled when the Mode status (SW0043) is 0 or 1. (during online)
Stores the count of the network event history.
This stored count is cleared when Event count clear (SB0009) is turned ON.
Stores the (cumulative) count that was detected for cable disconnections at the
PORT2.
When Clear communication error count (SB0006) is turned ON, the stored count is
cleared.
Stores the (cumulative) count that error data was received at the PORT2.
The count stores only error data that is not transmitted to all stations.
When Clear communication error count (SB0006) is turned ON, the stored count is
cleared.
(Conditions)
This is enabled when the Mode status (SW0043) is 0 or 1. (during online)
Stores the (cumulative) count that error data was received at the PORT2.
When Clear communication error count (SB0006) is turned ON, the stored count is
cleared.
(Conditions)
This is enabled when the Mode status (SW0043) is 0 or 1. (during online)
Stores the REMFR/REMTO execution status for each channel.
SW0080
Channel 1
SW008B
SW0081
Channel 2
SW008C
SW0082
Channel 3
SW008D
Channel 4
SW0083
SW008E
SW0084
Channel 5
SW008F
Channel 6
SW0085
SW0090
SW0086
Channel 7
SW0091
SW0087
Channel 8
SW0092
SW0088
Channel 9
SW0093
SW0089
Channel 10
SW0094
SW008A
Channel 11
SW0095
• 0: Normal completion
• 1 or higher: Abnormal completion (Page 167 Error Code List)
Channel 12
SW0096
Channel 23
Channel 13
SW0097
Channel 24
Channel 14
SW0098
Channel 25
Channel 15
SW0099
Channel 26
Channel 16
SW009A
Channel 27
Channel 17
Channel 28
SW009B
Channel 18
SW009C
Channel 29
Channel 19
SW009D
Channel 30
Channel 20
SW009E
Channel 31
Channel 21
SW009F
Channel 32
Channel 22
Availability
Master
Local
station
station

Hide quick links: