Error
Error code
code
D0E1H
Own station specified as reserved
D0E2H
Station No. duplication (own station)
D0E3H
Own station No. out of range
D0E4H
Multiple master stations (including
own station)
D0F0H to
Hardware error
D113H
D200H
Transient data received twice
D201H
Header information error in transient
data
D202H
Send buffer full
D203H
Read/write address error in transient
data
D204H
Network No. error in transient data
D205H
Target station No. error in transient
data
D206H
Network No. error in transient data
D207H
Incorrect number of relays specified
in transient data
D208H
Network No. error in transient data
D209H
Target station No. error in transient
data
D20AH
D20BH
Specified master station No. error in
transient data
D20CH
Current master station No. error in
transient data
D20DH
Transient data transmission
completion wait timeout
D20EH
Header information error in transient
data
D20FH
Target station No. error in transient
data
D210H
Target station No. error in transient
data
D211H
Own station No. undefined
(dedicated instruction)
D212H
Transient transmission failed
D213H
Transient data request error
16 TROUBLESHOOTING
168
16.9 Error Code List
Corrective action
In "Network Configuration Setting" of the master station, cancel the reserved station setting.
Change the station number of the own station to a station number that is not reserved.
Change the station number so that it will not be duplicated with any other station number.
After taking the above action, power OFF and then ON all the stations that detected the station number
duplication error, or reset them.
Add information of the own station to "Network Configuration Setting" of the master station.
Check the network condition by CC-Link IE Field Network diagnostics, and take action.
Check if the cables and switching hub are connected properly.
After taking the above action, power OFF and then ON all the stations that detected this error, or reset
them.
Refer to corrective action for hardware error. (Page 175 Hardware error)
Check the network condition by CC-Link IE Field Network diagnostics, and take action.
Check if the cables and switching hub are connected properly.
If the request source resides in another network, check if the routing parameters are correctly set, and
take corrective action.
Correct the header information at the request source, and retry the operation.
Reduce the frequency of transient transmission and then retry the operation.
When the mode of the master station is "Online (High Speed Mode)", change it to "Online (Normal
Mode)" and retry the operation.
Check if the cables and switching hub are connected properly.
Correct the read/write address at the request source, and retry the operation.
Correct the network number at the request source, and retry the operation.
If the request source resides in another network, check if the routing parameters are correctly set, and
take corrective action.
Correct the target station number at the request source, and retry the operation.
Correct the network number at the request source, and retry the operation.
If the request source resides in another network, check if the routing parameters are correctly set, and
take corrective action.
Correct the system configuration to reduce the number of relay stations to seven or less.
Check if the routing parameters are correctly set, and take corrective action.
Correct the network number at the request source, and retry the operation.
If the request source resides in another network, check if the routing parameters are correctly set, and
take corrective action.
Correct the target station number at the request source, and retry the operation.
Check the network condition by CC-Link IE Field Network diagnostics, and take action.
When the own station or target station detected an error, identify the cause of the error and take action.
Reduce the frequency of transient transmission and then retry the operation.
When the mode of the master station is "Online (High Speed Mode)", change it to "Online (Normal
Mode)" and retry the operation.
Check if the cables and switching hub of the request source are connected properly.
Correct the header information at the request source, and retry the operation.
Check if the command can be requested to all or a group of stations at the request source, and retry the
operation.
Correct the header information at the request source, and retry the operation.
Set the station number in the parameter setting, and retry the operation.
Check if the cables and switching hub of the request source are connected properly.
Exchange the cables between PORT1 and PORT2 of the request source and retry the operation.
Reduce the frequency of transient transmission and then retry the operation.
Correct the request command at the request source, and retry the operation.