EK280
7.2.4 Setting the network parameters
i
For parameterization of the EK280 you need a connection cable for the optical interface as well
as the enSuite program. enSuite can be downloaded free of charge from the Honeywell website
in the "Software Downloads" section:
www.elster-instromet.com/en/software-downloads
a) Closing the time windows
Time windows 1 to 4 must be closed for parameterization to function securely. To do this:
−
Connect a PC or laptop with enSuite installed to the EK280 optical interface using the connection
cable.
−
Start enSuite and establish the communication link to the EK280.
( chapter
3.1 Setting up the communication link to the EK280 via optical
−
Select "Navigation" on the left-hand side and then
navigation window.
−
In the top part of the device window, open the path "Parameters" > "Interfaces" by clicking on the
relevant plus signs, and then select
−
In call windows 1 to 4, set start and end to the same value for each one and then select the
changes to
device" icon at the top of the enSuite window.
−
Then wait a minute for any communications activity in progress on the EK280 to be safely stopped.
Application Manual
"Parameterize
"Call time
windows".
interface, p. 19)
online" at the bottom of the
96
"Transfer