I have an earth ground fault when the drive is on, however motor runs in bypass fine
1 comments:
Mr. Anderson
May 27, 2025
An earth ground fault in a Honeywell drive while the motor runs fine in bypass mode could be caused by insulation failure in the motor cables or the motor itself. Since the bypass mode does not use the drive, this suggests the drive detects the fault due to the current measurement showing an imbalance in motor phase currents, which indicates a possible ground fault in the motor or cables.
Need help?
Do you have a question about the NX series and is the answer not in the manual?
Questions and answers
I have an earth ground fault when the drive is on, however motor runs in bypass fine
An earth ground fault in a Honeywell drive while the motor runs fine in bypass mode could be caused by insulation failure in the motor cables or the motor itself. Since the bypass mode does not use the drive, this suggests the drive detects the fault due to the current measurement showing an imbalance in motor phase currents, which indicates a possible ground fault in the motor or cables.