7.4.11.2 EK280 Parameterization
i
For parameterization of the EK280 you need a connection cable for the optical interface as well
as the enSuite program. enSuite can be downloaded free of charge from the Honeywell website
in the "Software Downloads" section:
www.elster-instromet.com/en/software-downloads
a)
Closing the time windows
In order that the parameterization works correctly the time windows 5 and 6 must be closed. To do this:
Connect a PC or laptop with enSuite installed to the EK280 optical interface using the connection
cable.
Start enSuite and set up the communication link to the EK280.
( chapter
3.1 Setting up the communication link to the EK280 via optical
Select "Navigation" on the left-hand side and then
navigation window.
In the top of the device window open the path "Parameter" > "Interfaces" by clicking on the relevant
plus signs, and then select
In call windows 5 and 6 set start and end to the same value for each one and then select the
"Transfer changes to device" icon at the top of the enSuite window.
Then wait a minute, for any communications activity in progress on the EK280 to be safely stopped.
b)
Send parameter file
Send the parameter file to the EK280 ( chapter
EK280_xvx. - FE260 & int. RS232 interface card (*)
For the following customized settings and tests required, press "Navigation" on the left-hand side
and then
"Parameterize
i
All the values listed in enSuite under "Parameters" can be found on the "Serv." display tab of the
EK280 under the same path.
c)
Setting time window for potential data retrievals
In the base configuration now displayed you can define time windows, during which data can be cyclically
retrieved from the EK280 via this interface. Time windows 5 and 6 are reserved for EK280 operation with an
FE260, and generally only time window 5 is used. Redundant time windows can be deactivated by setting
the time window start and end to the same value.
In the top of the device window open the path "Parameter" > "Interfaces" by clicking on the relevant
plus signs, and then select
For call window 5, set the start to "00:00" and the end to "23:59" and then select the "Transfer
changes to device" icon at the top of the enSuite window.
Wait for around a minute for the EK280 to detect the FE260.
34
The "x" stands for the version of software on the device, e.g. "2v2".
The star * stands for a small letter which indicates the version of the file, e.g. "a".
Application Manual
"Call time
windows".
online" at the bottom of the navigation window.
"Call time
windows".
"Parameterize
online" at the bottom of the
3.6 Send parameter