The two battery-power time windows are set in the enSuite device window under:
-
Parameter > Interfaces > Connections > Connection 1
-
Parameter > Interfaces > Connections > Connection 2
The four mains voltage time windows are set under:
-
Parameter > Interfaces > Connections > Connection 3
-
Parameter > Interfaces > Connections > Connection 6
If you do not need a time window, you can deactivate it by setting the time window start and end to the same
value.
Press
"Transfer changes to
7.5.5.3 Parameterization of the DM130 analog modem
The DM130 can be parameterized in three ways:
On site by means of a DIP switch in the DM130
On site via the RJ10-type running RS232 interface of the DM130
Remotely via a modem connection
The easiest way is the configuration by means of a DIP switch. In this way, all the necessary EK280
operations settings can easily be performed on site. The switch can only be set up after opening the housing
cover.
CAUTION! Danger!
Ensure the mains voltage is disconnected before opening the DM130 housing, ensure it is
not turned back on and verify that there is no voltage!
The necessary settings for the operation of an EK280 are shown in the table below:
D1
D2
D3
D4
0
0
0
0
After switching on the mains voltage, the modem can be reset via the service button on the DM 130. The
service button is located to the right of the RS232 interface. If it is longer than 5 seconds, the value (0 or 1)
of the switch is evaluated and the parameters in the Modem is set appropriately. The effectiveness of the
DIP switch creation is indicated by a yellow flashing LED status light.
For the optional parameter assignment via the RS232 interface or via a modem connection, you need the
DMSET configuration program. For operation instructions, please refer to the relevant documentation of the
DM130 or the DMSET configuration program.
Application Manual
device" icon at the top edge of the enSuite window.
D5
D6
D7
D8
D9
0
1
0
1
1
and
to
D10
Description
V42 / V42.bis / MNP active
Password protection is not active.
Answer after 1 ring
Multistandard handshake telephone line
Local baud rate is 19200 bit/sec
Mode C operation, fixed baud rate
1
Character format 8N1 local