1. Select the digital input/output on the required terminal.
2. Interconnect the signal source of the digital input (8 to 15).
OR
3. Proceed as follows to change the digital input into a digital output:
– Click the selector.
– Then connect the signal sink of the digital output (8 to 15).
– If you want to invert the digital output, click on this icon
4. Repeat steps 2 or 3 for all digital inputs/outputs of the required terminal.
6.1.2.3

Measuring sockets

The measuring sockets output the analog signals. Any freely interconnectable signal can be
output at any measuring socket. A measuring socket can be used, for example, to output the
actual speed value (r0063) to a measuring instrument connected to the measuring socket.
Note
Only for commissioning and service
The measuring sockets may only be used for commissioning and service purposes. The
measurements may be performed only by appropriately trained skilled personnel.
You can make the following settings:
● Activate the limitation to a characteristic.
● Interconnect signal sources.
● Parameterize a characteristic.
● Define an offset.
Procedure
1. Select one of the following settings in the "Limitation" drop-down list of a measuring
socket:
– Limitation On
– Limitation Off
Getting Started, 12/2018, 6SL3097-5AG30-0BP0
When inverted, the icon looks like this
"Drive control > Parameters > Inputs/outputs > Measuring sockets"
If signals are output outside the permissible measuring range, the signal is limited to
4.98 V or to 0 V.
The output of signals outside the permissible measuring range causes a signal
overflow. In the event of an overflow, the signal jumps from 0 V to 4.98 V or from 4.98
to 0 V.
Performing basic parameterization
.
.
6.1 Control Unit
123